I Series Features Comparison

(ROTATE YOUR SCREEN)

Capacity10KVA 9KW20KVA 18KW30KVA 27KW40KVA 36KW60KVA 54KW80KVA 72KW100KVA 90KW120KVA 108KW
Input
Rated Voltage 380V/400V/415VAC
Voltage Range
Rated Frequency 50/60Hz Auto Sensing
Frequency Range 40-70Hz
Power Factor ≥0.99
Total Harmonic Distortion (THDi) ≤3%
Bypass Voltage Range 380V-40%~380V+20%(Settable via LCD)
Output
Voltage 380V/400V/415VAC
Voltage Regulation ±1%
Frequency Synchronized with utility on AC mode;  50/60Hz±0.1% on battery mode
Waveform Pure sine wave
Crest Factor 03:01:00 AM
Total Harmonic Distortion(THDV) ≤1%(Linear load);≤3%(Non-linear load)
Transfer Time AC mode to battery mode :0ms Inverter mode to bypass mode:0ms
Inverter Overload Capability 
Bypass Overload Capability
Batterie
DC Voltage ±192V(Option:±204V/±216V/±228V/±240V)
Inbuilt Battery of Standard Model 32*12V/9Ah 64*12V/9Ah NO
Charger Current 1-12A (Setting available via LCD) 1-24A(Setting available via LCD) 1-24A(Setting available via LCD)1-48A(Optional)
System
Efficiency ≥93% (Online mode);  ≥98.5% (ECO model)
Display Panel 5.7 Inches LCD touch screen
Alarm Battery mode, Battery voltage low, Fans fault etc
Maximum Parallel number 6
EMI EN62040-2
EMS
IEC61000-4-2(ESD)
IEC61000-4-3(RS)
IEC61000-4-4(EFT)
IEC61000-4-5(Surge)
Environment
Humidity 0~95% RH @ 0~40℃(non-condensing)
Noise Level ≤60dB
Management
Communication
RS232,RS485,USB,Dry contact
Supports Windows 98/2000/2003/XP/Vista/2008/7/8
Optional SNMP Power management from SNMP manager and web browser
Physical
Dimension(mm) W*D*H 600*800*1360 600*800*1680
Packing Dimension(mm) W*D*H 720*920*1500 720*920*1820
Net/Gross Weight(kg) Without Inbuilt battery 180/200 185/205 190/210 225/245 230/250 336/376 374/414

New Account Register