Input |
Rated Voltage |
380V/400V/415VAC |
Voltage Range |
|
Rated Frequency |
50/60Hz Auto Sensing |
Frequency Range |
40-70Hz |
Power Factor |
≥0.99 |
Total Harmonic Distortion (THDi) |
≤3% |
Bypass Voltage Range |
380V-40%~380V+20%(Settable via LCD) |
Output |
Voltage |
380V/400V/415VAC |
Voltage Regulation |
±1% |
Frequency |
Synchronized with utility on AC mode; 50/60Hz±0.1% on battery mode |
Waveform |
Pure sine wave |
Crest Factor |
03:01:00 AM |
Total Harmonic Distortion(THDV) |
≤1%(Linear load);≤3%(Non-linear load) |
Transfer Time |
AC mode to battery mode :0ms Inverter mode to bypass mode:0ms |
Inverter Overload Capability |
|
Bypass Overload Capability |
|
Batterie |
DC Voltage |
±192V(Option:±204V/±216V/±228V/±240V) |
Inbuilt Battery of Standard Model |
32*12V/9Ah |
64*12V/9Ah |
NO |
Charger Current |
1-12A (Setting available via LCD) |
1-24A(Setting available via LCD) |
1-24A(Setting available via LCD)1-48A(Optional) |
System |
Efficiency |
≥93% (Online mode); ≥98.5% (ECO model) |
Display Panel |
5.7 Inches LCD touch screen |
Alarm |
Battery mode, Battery voltage low, Fans fault etc |
Maximum Parallel number |
6 |
EMI |
EN62040-2 |
EMS |
IEC61000-4-2(ESD) |
IEC61000-4-3(RS) |
IEC61000-4-4(EFT) |
IEC61000-4-5(Surge) |
|
Environment |
Humidity |
0~95% RH @ 0~40℃(non-condensing) |
Noise Level |
≤60dB |
Management |
Communication |
RS232,RS485,USB,Dry contact |
Supports Windows 98/2000/2003/XP/Vista/2008/7/8 |
|
Optional SNMP |
Power management from SNMP manager and web browser |
Physical |
Dimension(mm) W*D*H |
600*800*1360 |
600*800*1680 |
Packing Dimension(mm) W*D*H |
720*920*1500 |
720*920*1820 |
Net/Gross Weight(kg) Without Inbuilt battery |
180/200 |
185/205 |
190/210 |
225/245 |
230/250 |
336/376 |
374/414 |